TRASDUCER RPV-V1-Ρ1-03 IN:150V AC:120V OUT:4-20mA

[Sign in to view price]
RPV-V1-Ρ1-03
Request offer
 

Specifications

  • Accuracy ( 23 + 5 oC ) : 0.2% ro (avg.), 0.4% ro (Trms)
  • Stability : Maximum 100ppm/oC, less than 0.2% drift per year typically
  • Input burden : 0.3VA / element typically, self-powered type 1VA / element typically
  • Frequency : 50 + 2 Hz ; 60 + 2 Hz
  • Maximum input over :
  • Current related input : 2 * rated continuous, 10 * rated 10 sec, 25 * rated 2 sec, 50 rated 1 sec
  • Voltage related input : maximum 2 * rated continuous ( 150V / 300V ), self powered mode 1.5 rated continuous ( 500V )
  • Output load :
  • DC current mode : maximum 10V drop
  • DC voltage mode : maximum 5mA drive
  • Response time & ripple < 400ms for step change 0-95%, ripple less than 0.5% ro peak-peak
  • Magnetic effect < 0.05% change 1M center 100 amp per turn, synchronized with line frequency
  • Aux. power effect < 0.005% for per voltage change
  • 4KV AC rms 1 minute between terminals to case; fulfills IEC 688 standards
  • 2KV AC rms 1 minute between input / output / power; fulfills IEC 688 standards
  • Dielectric strength :
  • Impulse / SWC : IEC 255-4, 5KV 1.2*50us, IEC255-22-1, 2.5KV ( 1MHz / 400Hz )
  • Operating condition : -5 to 60oC, 20 to 99% RH non condensing
  • Storage condition : -20 to 70oC, 20 to 99% RH non condensing
  • Radio screening : RFI degree N complies with VDE 0875
  • AC 120V / 240V + 15%, 2 wires ( 8~36V DC powered ), 50 / 60Hz
  • < 3VA for RPA, RPV, RPAR, RPVR; 8VA for RPAX, RPVX
  • Enclosure code : Case IP 50 / terminals IP 30, complies with IEC 529, BS 5490 DIN 40050
  • Power supply :
Brands: